Post Static and Dynamic Thresholds

The POST (power on self test of the bridge) performs two tests. The limits are not configurable.

1) The POST static gating test measures the voltage on each of the three phases before the bridge is enabled. The three voltages must measure 50% (+/- 25%) of Battery Voltage to pass.

2) If the static test passes the POST dynamic gating test enables and pwm’s only one of the 6 FETS at a time. The 3 low side voltages must measure 15% (+/- 10%.) of Battery Voltage. The three high side FETS must measure 85% (+/- 10%) of Battery Voltage.

The tests happen each time you enable a motor (if the motor is not already turning).

When you get static errors you can actually just read the live phase A voltage (B and C as well) and test results.

POST static gating test registers:

Name Description Units Address
285
286
287
47
306
307
308

POST dynamic gating test registers:

Name Description Units Address
48
300
301
302
303
304
305